Commercial Refrigeration rebates

Commercial refrigeration display case door retrofit

Rebate: $100 to $200 per linear foot of case

Commercial refrigeration display case door retrofit rebate form

Eligibility

  • Available for retrofits only.
  • Existing display case must be open (i.e., not have doors).
  • Existing display case must be served by a remote refrigeration system (i.e., not self-contained).
  • The vertical case measure is available for medium-temperature display cases.
  • The horizontal case measure is available for either medium or low-temperature cases. Dual temperature cases should be reported as medium temperature.
  • Postconditions:
    • Display case must have double – or triple-pane glass doors.
    • Replacing an open case with a new case with double- or triple-pane glass doors is eligible.
Commercial refrigeration evaporator fan motors

Rebate of $55 to $140 per motor

Commercial refrigeration evaporator fan motors rebate form

Eligibility

  • Incentives are for retrofits only.
  • For walk-in coolers and freezers: Motors must have fans that are 10 inches in diameter or larger.
  • For refrigerated display cases: All fan sizes are eligible.
  • Pre-condition:
    • Shaded pole evaporator motor in refrigerated display case, walk-in cooler or freezer.
  • Post-conditions:
    • Replace a shaded pole evaporator fan motor with an ECM or PMSM.
Commercial refrigeration floating pressure controls

Rebate of $10 to $20 according to BPA refrigeration controls calculator V1.0

Commercial refrigeration floating display pressure controls rebate form

Eligibility

  • Available for retrofits only.
  • This measure applies to multiplex refrigeration systems (i.e., compressors operating in parallel) only.
  • The measure unit is evaporator design load in MBH.
  • Implementation requires use of the BPA Refrigeration Controls Calculator, and the MBH in the submitted calculator must match the highlighted or circled MBH in the submitted refrigeration schedule. The end-user can apply for either the Floating Head Pressure Control Measure, the Floating Suction Pressure Control Measure, or both, as indicated in the calculator.
  • Floating Head Pressure Control:
    • Pre-condition – The minimum head pressure temperature set point must be fixed and have exceeded or been equal to 80 degrees Fahrenheit.
    • Post–condition – Minimum head pressure control set point must be 70 degrees Fahrenheit.
  • Floating Suction Pressure Control:
    • Pre–condition – The base case must be a fixed suction pressure or temperature set point, as noted in the calculator.
    • Post–condition – post-project suction pressure shall be enabled to float, as indicated in the BPA Refrigeration Controls Calculator, based on input from a temperature sensor in a critical case on the appropriate suction group.